防回流阀

Requirements and registration\r\n

'Backflow' is water that flows backwards into our pipes after a property has used it. This water may carry contaminants that can harm people's health. That's why backflow prevention is so important, and backflow prevention containment devices must meet our connection requirements. We have a guide that provides information for backflow prevention (1MB) containment and a collection of frequently used Backflow prevention terms (66KB).

\r\n"}}" id="text-432663e3e0" class="cmp-text">

要求及注册

“回流”是指物业使用后,水回流到我们的管道中。这些水可能携带有害人体健康的污染物。这就是为什么防回流阀是如此重要,而防回流密封装置必须满足我们的连接要求。我们有一个提供信息的指南防回流(1MB)容器和常用的集合防回流条款(66KB)

立即注册提交回流测试报告
你要做的第一件事是注册防回流使用有效的电子邮件地址。如果您是Sydney Water Tap in的注册用户,您可以向防回流应用程序提交访问请求,在登录细节中引用您的Tap。


When a site needs backflow containment\r\n

All connections to our water mains must have suitable backflow containment as set out in our policy, Your responsibilities when connected to our services (358KB)

\r\n

What plumbers must do

\r\n

Licensed plumbers must assess each site to work out its specific backflow containment needs.
\r\n
\r\nIf you've determined the site's hazard rating as low, our 20mm and 25mm water meters already have a simple backflow prevention device in them. If the property's water meter is larger than 25mm, you'll need a separate backflow device. Find out more about meters and metered standpipes.
\r\n
\r\nYou must advise the property owner of the backflow requirements and install a backflow prevention device appropriate to the property's hazard rating. You must also tell the owner if the device needs to be tested each year. 

\r\n"}}" id="ID01" class="cmp-text">

当站点需要防回流时

所有接驳本署水管的接驳处,必须按本署的政策订明,设有适当的防回流装置。你的责任连接到我们的服务(358KB)

水管工该做什么

持牌水管工必须对每个工地进行评估,确定其具体的防回流需求。

如果你已经确定现场的危险等级较低,我们的20mm和25mm水表已经有一个简单的防回流装置。如果物业的水表大于25mm,您将需要一个单独的回流装置。了解更多关于仪表和仪表立管

您必须将防回流要求告知业主,并安装适合于该物业的危险等级的防回流装置。您还必须告知设备的所有者是否需要每年进行测试。


What to know about fire services
\r\n\r\n

All fire services, fire hydrant and sprinkler services require the installation of a Double Check Detector Assembly (DCDA).
\r\n
\r\nThe materials used on the upstream side of the Double Check Detector Assembly (DCDA) and including the outlet control valve must be WaterMark approved for plumbing and drainage installations.
\r\n
\r\n
There can be no galvanised pipe and fittings on the upstream/inlet side of the containment device.

\r\n
    \r\n
  • All rising spindle valves must be WaterMark approved.
  • \r\n
  • All butterfly valves must be WaterMark approved and gear operated.
  • \r\n
\r\n

If you need further information, email us at backflow@sydneywater.com.au.

\r\n"}}" id="ID02" class="cmp-text">

关于消防服务要知道些什么

所有消防服务,消火栓和洒水服务要求安装双止回检测器组件(DCDA)。

双止回检测器组件(DCDA)上游使用的材料和包括出口控制阀必须是水印批准用于水管及排水装置。

可能会有没有安全壳装置上游/进口侧的镀锌管和配件。

  • 所有上升主轴阀必须经过水印认证。
  • 所有蝶阀必须经过水印认证,并采用齿轮操作。

如果您需要进一步的信息,请发邮件给我们backflow@sydneywater.com.au


Who to contact about zone and individual devices\r\n

We no longer accept reports for zone and individual backflow devices. Contact NSW Fair Trading if you have any questions about these type of devices.

\r\n"}}" id="ID03" class="cmp-text">

关于分区和单个设备应该联系谁

我们不再接受区域和单个回流设备的报告。联系新南威尔士州公平贸易如果你对这类设备有任何疑问。


Who can install or test backflow prevention devices\r\n

Only licensed plumbers with backflow prevention accreditation issued by a registered training organisation (backflow plumbers) can inspect, commission and test medium and high hazard backflow devices.
\r\n
\r\nOnce backflow devices have been installed, only backflow plumbers can test them. Once a test has been done, backflow plumbers must submit the test report using our online lodgement system.
\r\n
\r\nSoon, all plumbers will be able to tell us about the installation of low hazard devices via Sydney Water Tap in.

\r\n"}}" id="ID04" class="cmp-text">

谁可以安装或测试防回流装置

只有持有注册培训机构发出的防止水喉倒流认证的持牌水喉匠(“水喉倒流匠”)才可进行检查、委任及测试中、高危险回流装置。

一旦安装了回流装置,仅限倒流管道工可以测试他们。一旦测试完成,回流管道工必须使用我们的网上递交系统

很快,所有的水管工可以告诉我们安装的情况低风险设备通过悉尼自来水

你在我们的名单上吗回流水管工?
如果你已经被认可并想要加入我们的名单,请将你的学历证书副本通过电子邮件发送至backflow@sydneywater.com.au或者打电话给我们13 20 92。
如果您想成为一名合格的回流管道工,请访问TAFE NSW搜索“管道”或“回流”。


Why you need to retain photos for each lodgement\r\n

We now audit lodgements.
\r\n
\r\nAs part of our audit, we may ask you to provide 2 photographs for any backflow containment device test you've registered with us. The photos need to show:

\r\n
    \r\n
  • the backflow device you tested with the serial number clearly visible
  • \r\n
  • the test kit you used.
  • \r\n
\r\n

You don't need to attach photographs to your test reports when you upload them using the new backflow prevention application. However, your uploaded test reports may be subject to an audit. If we audit your lodgement, we'll send you an email asking you to email the photographic evidence to us as proof. 

\r\n"}}" id="ID05" class="cmp-text">

为什么每次提交时都要保留照片

我们现在审计提交的文件。

作为我们审核的一部分,我们可能会要求您为在我们注册的任何防回流装置测试提供两张照片。照片需要显示:

  • 你测试的回流装置序列号清晰可见
  • 你用的测试套件。

当您使用新的防回流应用程序上传测试报告时,不需要将照片附加到测试报告中。但是,您上传的测试报告可能会受到审核。如果我们审核您的住宿,我们将发邮件给您,请您将照片证据通过电子邮件发给我们作为证明。

请注意
我们不会审核您使用新的防回流应用程序上传的第一个测试报告。但是,我们将审核第二次和以后的测试报告。


How to submit a backflow test report\r\n

Use our online lodgement system to submit your backflow test report. To access the system for the first time, you'll need to register for backflow prevention using your personal email address.

\r\n"}}" id="ID06" class="cmp-text">

如何提交回流测试报告

使用我们的网上递交系统提交您的回流测试报告。要第一次访问系统,您需要注册防回流使用你的个人电子邮件地址。

If you can't access the system, email us at backflow@sydneywater.com.au

\n"}}" id="text-76ae698272" class="cmp-text">

如果您无法进入系统,请发邮件给我们backflow@sydneywater.com.au


Baidu